Please use this identifier to cite or link to this item: http://hdl.handle.net/11189/8499
DC FieldValueLanguage
dc.contributor.authorKrishnamurthy, Senthilen_US
dc.contributor.authorBaningobera, Bwandakassy Elengaen_US
dc.date.accessioned2022-06-10T09:54:57Z-
dc.date.available2022-06-10T09:54:57Z-
dc.date.issued2019-
dc.identifier.citationKrishnamurthy, S. & Baningobera, B.E. 2019. IEC61850 standard-based harmonic blocking scheme for power transformers. Protection and Control of Modern Power Systems, 4(10): 1-15. [https://doi.org/10.1186/s41601-019-0123-7]en_US
dc.identifier.issn2367-0983-
dc.identifier.urihttp://hdl.handle.net/11189/8499-
dc.description.abstractTransformer Differential and overcurrent schemes are traditionally used as main and backup protection respectively. The differential protection relay (SEL487E) has dedicated harmonic restraint function which blocks the relay tripping during the transformer magnetizing inrush conditions. However, the backup overcurrent relay (SEL751A) applied to the transformer protection does not have harmonic restraint element and trip the overcurrent relay during the inrush conditions. Therefore, major contribution of this research work is the developed harmonic blocking scheme for transformer which uses element (87HB) of the transformer differential relay (SEL487E) to send an IEC61850 GOOSE-based harmonic blocking signal to the backup overcurrent relay (SEL751A) to inhibit from tripping during the transformer magnetizing inrush current conditions. The simulation results proved that IEC61850 standard-based protection scheme is faster than the hardwired signals. Therefore, the speed and reliability of the transformer scheme are improved using the IEC61850 standard-based GOOSE applications.en_US
dc.language.isoenen_US
dc.publisherSpringeren_US
dc.relation.ispartofProtection and Control of Modern Power Systemsen_US
dc.subjectTransformer protectionen_US
dc.subjectOvercurrent protectionen_US
dc.subjectDigital protection schemeen_US
dc.subjectCurrent differential protectionen_US
dc.subjectTransformer magnetizing inrush currenten_US
dc.subjectHarmonic blockingen_US
dc.subjectIEC 61850en_US
dc.subjectGOOSE messageen_US
dc.titleIEC61850 standard-based harmonic blocking scheme for power transformersen_US
dc.identifier.doihttps://doi.org/10.1186/s41601-019-0123-7-
dc.typeArticleen_US
Appears in Collections:Eng - Journal articles (DHET subsidised)
Files in This Item:
File Description SizeFormat 
IEC61850_standard-based_harmonic.pdfArticle4.01 MBAdobe PDFView/Open
Show simple item record

Page view(s)

190
Last Week
0
Last month
2
checked on Sep 2, 2026

Download(s)

114
checked on Sep 2, 2026

Google ScholarTM

Check

Altmetric


Items in Digital Knowledge are protected by copyright, with all rights reserved, unless otherwise indicated.